Does a receptacle close to the tub or sink need GFCI protection in Ontario?
Receptacle near a bathtub, shower, or bathroom sink — Does a receptacle close to the tub or sink need GFCI protection?
Yes. Any 5-15R or 5-20R receptacle within 1.5 m of a sink, bathtub, or shower stall must have Class A GFCI protection (Rule 26-704). Keep receptacles out of the tub or shower space itself — at least 1 m away where practicable, and never less than 500 mm (Rule 26-720).
⚑ WATCH OUT FOR THIS
No receptacle may be placed in a bathtub or shower stall itself, and faces must not point up on a counter or down where water pools.
Code book: OESC 29th ed. (2024) — Rules 26-704 & 26-720: Receptacles — GFCI protection
Help only — check the rule in the real code book before you trust it. This does not take the place of an ESA inspection.